MODBUS Settings
Enter the MODBUS parameters used on the network.
Figure 25: MODBUS settings
• Slave address: enter the node or slave address for the SIM (see the manual section: Using IntelliSense
®
with MODBUS RTU Networks)
• Select the appropriate serial parameters (table 3)
• Select the line baud rate between 4,800 and 115,200 bps
Table 3: MODBUS parameters
Data Bits Parity Stop Bit
8 None 1
8 Even 1
8 Odd 1
8 None 2
8 Even 2
8 Odd 2
SIM Maintenance Functions
The following commands are available:
Restart SIM: Cycles power to the SIM.
Set Time: Sets the date and time on the SIM to match those of the Data Gate-
way or PC.
Backup Settings: The current SIM settings are downloaded to an XML le on the
user’s machine.
Restore Settings from Backup: The user can upload SIM settings from a previ-
ously saved XML le backup.
Restore SIM to Factory Settings: Removes all user changes, and restores the
SIM to default settings.
Reset predictive data and history: Deletes all snapshot history of changes in
the cylinder performance. Recommended when new cylinder is installed.
Update SIM Firmware: Prompts the user to select the new rmware le. See the
update rmware section in this manual for details.
Blink LEDs: This causes the SIM to ash all indicator LEDs for a few seconds, allowing it to be identied.